Saya berusaha mengingat-ingat bahwa saya tidak pernah menjumpai engineering specification dan drawing yang membahas secara detail, menggambarkan secara detail typical drawing tentang guideline pemasangan (mana accessories yang perlu, mana accessories yang tidak diperlukan), dan urutan (jangan terbalik) pemasangan cable gland accessories: Sealing / IP washer, Earth Tag, Serrated Washer, Reducer, Adaptor, dan Lock Nut.

Namun demikin aktivitas Quality Inspection di Site memberikan porsi besar pada inspeksi detail kabel gland dan accessoriesnya tersebut  berdasarkan best practice pengalaman proyek sebelumnya, module-module / diktat training, dan manufacture recommendation. Efek yang dihasilkan jika ditemukan ketidak-sesuaian adalah sangat menyakitkan yaitu bongkar terminasi dan bongkar kabel gland yang berefek langsung pada delay schedule.

Jangan-jangan Engineering menganggap tidak penting dan dianggap hal remeh temeh, sedangkan Quality menganggap penting accessories tersebut? Yang jelas it costs too much for construction progress jika hasilnya adalah selalu bongkar. Dan uniknya dari proyek-proyek yang saya jumpai selalu terjadi yang namanya Bongkar gara-gara cable gland accessories. Gland accessories antara lain sebagai berikut:

  • Sealing / IP Washer adalah Ring Gasket untuk menjamin air, gas, atau dust dapat lalu lalang melalui sela-sela antara gland dan enclosure. Dengan memasang IP washir maka rating Ingress Protection tetap terjamin. Meskipun dikatakan oleh salah satu manufacture ketika gland paralel thread (metric) bertemu hole paralel thread (metric) dan saling kontak gigit minimal 6mm maka tanpa tambahan IP washer pun sudah masuk kriteria IP54. Lain halnya dengan tappered thread , sealing / IP washer tidak perlu digunakan.
  • Earth Tag adalah cantolan grounding. Untuk memastikan bahwa cable gland terhubung dengan grounding. Ketika cable gland terhubung dengan conductive enclosure maka dianggap gland sudah bersatu dengan enclosure sehingga grounding enclosure jadi satu dengan grounding cable gland. Ketika enclosue beruba non-conductive material maka maka fungsi earth tag adalah untuk menggrounding gland.
  • Serrated washer adalah ring metalic bergerigi yang berfungsi sebagai anti vibration sehingga kalau ada vibrasi tidak mengendorkan gland. Namun demikian serrated washer seperti mandapatkan fungsi “baru” sebagai pengoyak enclosure metalic conductive yang dilapisi cat, agar cable gland menyentuh metalic enclosure tanpa halangan cat.
  • Reducer adalah fitting untuk menyesuaikan lubang perempuan thread yang terlalu besar dengan thread gland yang kecil. Kalau sebaliknya bagaimana? Lubang thread enclosure terlalu kecil sementara glandnya terlalu besar maka biasa disebut adaptor (harusnya disebut Expander). Adaptor juga untuk menyebut fitting untuk menyesuaikan tipe thread (parallel atau tappered) yang tidak sesuai antara lubang perempuan dan thread gland
  • Lock Nut adalah mur pengunci thread gland agar terikat kuat pada enclosure.

Ketika semua pihak menganggap pemasangan gland accessories adalah hal penting dan kritikal, maka tentu akan dikeluarkan berbagai macam kombinasi Typical Cable Gland and Accessories Installation. Fungsinya sebagai guidance electrican lapangan untuk mengurangi re-work bongkar-pasang cable gland. Typical Cable Gland and Accessories Installation terdiri kurang lebih sebagai berikut. Kombinasinya berdasarkan tipe lubang: Hole Through, Tappered Thread, atau Parallel Thread; Ukuran dan Tipe Lubang Fit atau Unfit; dan Enclosure (JB atau Panelnya) metalic conductive atau non-conductive.

  1. Typical Cable Gland and Accessories Installation for Fit Hole Through Painted Conductive Enclosure
  2. Typical Cable Gland and Accessories Installation for Fit Hole Through Unpainted Conductive Enclosure
  3. Typical Cable Gland and Accessories Installation for Fit Hole Through Non-Conductive Enclosure
  4. Typical Cable Gland and Accessories Installation for Unfit Hole Through Painted Conductive Enclosure
  5. Typical Cable Gland and Accessories Installation for Unfit Hole Through Unpainted Conductive Enclosure
  6. Typical Cable Gland and Accessories Installation for Unfit Hole Through Non-Conductive Enclosure
  7. Typical Cable Gland and Accessories Installation for Fit Tappered Thread (NPT) Gland on Tappered Hole Thread Conductive Enclosure (Regardless Painted or Non-Painted)
  8. Typical Cable Gland and Accessories Installation for Unfit Tappered Thread (NPT) Gland on Tappered Hole Thread Conductive Enclosure (Regardless Painted or Non-Painted)
  9. Typical Cable Gland and Accessories Installation for Fit Parallel Thread (Metric) on Conductive Enclosure
  10. Typical Cable Gland and Accessories Installation for Fit Parallel Thread (Metric) on Non-Conductive Enclosure
  11. Typical Cable Gland and Accessories Installation for Unfit Parallel Thread (Metric) on Conductive Enclosure
  12. Typical Cable Gland and Accessories Installation for Unfit Parallel Thread (Metric) on Non-Conductive Enclosure
  13. Typical Cable Gland and Accessories Installation for Unfit Tappered Thread (NPT) Gland to Parallel Thread (Metric) on Conductive Enclosure
  14. Typical Cable Gland and Accessories Installation for Unfit Tappered Thread (NPT) Gland to Parallel Thread (Metric) on Non-Conductive Enclosure
  15. Typical Cable Gland and Accessories Installation for Unfit Parallel Thread (Metric) Gland to Tappered Thread (NPT) on Conductive Enclosure
  16. Typical Cable Gland and Accessories Installation for Unfit Parallel Thread (Metric) Gland to Tappered Thread (NPT) on Non-Conductive Enclosure

Ada 16 kombinasi racikan Rujak (Eh salah…. Cable Gland Accessories)  yang menghasilkan kombinasai racikan Sealing / IP washer, Earth Tag, Serrated Washer, Reducer, Adaptor, dan Lock Nut yang agak berbeda. Concern-concern yang menyebabkan perbedaan kombinasi di atas antara lain.

  1. Beda Painted dan Non-painted enclosure pada hole through (lubang lewat) adalah gigitan pada enclosure. Catnya kalau tidak digigit menghalangi kontak antara gland dengan enclosure. Siapa yang menggigit enclosure sehingga cable gland bisa nyambung alias conductive dengan enclosure?. Karena tidak ada gigitan maka  kadang diminta serrated washer sebagai penggigit.
  2. Beda Conductive (metalic) dan Non-Conductive (GRP, Fiber, Plastic) adalah efek grounding dari cable gland apakah bisa bersatu dengan enclosure atau tidak. Efek dari kasus ini adalah penggunaan Earth Tag diperlukan atau tidak.
  3. Beda Fit dan Unfit Hole Through akan menyebabkan penggunaan Reducer atau Adapter, di mana lokasi dipasang IP Washer apakah antara enclosure dengan reducer dan atau reducer dengan gland?.
  4. Beda Hole Through dan Thread (NPT) akan berefek pada beda gigitan antara gland dengan enclosure dan kekuatan menahan gland pada enclosure (lock nut).
  5. Ketika gland dipasang pada unfit hole thread atau unfit hole through maka dimana earth tag akan dipasang? apakah antara enclosure dengan reducer / adapter atau antara reducer/ adapter dengan gland?
  6. Ketika gland dipasang pada unfit hole thread atau unfit hole through yang memerlukan reducer apakah IP washer perlu dipasang? Kalau perlu apakah dipasang antara enclosure dengan reducer atau antara reducer dengan gland? Atau diperlukan dua-duanya?
  7. Vibration apakah perlu serrated washer?
  8. ……………………………………………………

Selama tidak ada referensi engineering detail tentang hal-hal di atas menurut saya dipersilahkan untuk meracik gland accessories berdasarkan best practice, pengalaman, dan training-training. Yang terpenting fungsi accessories mampu:

  • Memastikan Grounding Continuity dari Gland ke Earth PE
  • Memastikan Sealing untuk menjamin IP protection menghalangi yang lewat
  • Mengurangi Vibrasi
  • Memastikan Secara mekanik cable gland terpasang dengan kencang

Dan secara keseluruhan racikan accessoris dan body cable glandnya sendiri berfungsi melakukan proteksi dari timbulnya ledakan. Memisahkan gas, oksigen, dan sumber percikan api tidak saling bertemu.

Batam, 02 Des 2018

Nova Kurniawan

Advertisements

Leave a Reply

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out /  Change )

Google photo

You are commenting using your Google account. Log Out /  Change )

Twitter picture

You are commenting using your Twitter account. Log Out /  Change )

Facebook photo

You are commenting using your Facebook account. Log Out /  Change )

Connecting to %s

%d bloggers like this: